We use cookies to support this website, track usage on this website, to perform analytics and to perform promotional activities. Click here to accept cookies.
TIC's Cookie Policy. Privacy Policy

Related Information

Err5: Communication time-out (RS485)

Cause:
Err5: Communication time out error (RS485) occurs when the communication between an external device and the RS485 communications on the ASD times out.
Clearing:
Check the wiring between the external RS485 device and the input on the ASD. Verify that external device is powered on and operating correctly. Inspect the motor and driven equipment for issues prior to clearing any faults. Use one of the following methods to clear the fault.
• The [STOP/RESET] button on the AS3 keypad was pressed twice in quick succession
• Activate a digital input that has been programmed to “Reset” function
• Set the tyP (F007) Parameter to: 4: Clear past trips
Discussion

Please reference latest AS3 Instruction Manual more details or latest information.

AS3 fault codes, descriptions, symptoms and suggested remedies can be found in the below links. Each fault code can also be linked to directly from the AS3 by accessing the QR code on a mobile device while the AS3 is currently experiencing the fault.

Need a Quote? Have A Question?
x









Processing...
Top Top