OL3: Overload (IGBT)

Cause:
1) While operating the low-speed range (15 Hz or less) with high carrier frequency, overload occurred.
2) Momentary power failure occured, and tried to start the rotating motor.

Clearing:
1)
• Reduce the load.
• Lower the carrier frequency[F300:Carrier Frequency]. Or set [F316: Carrier frequency control] to "Valid decrease".
• Increase the output frequency.
•Reduce the level of [F601: Stall prevention level 1] or [F185:Stall protection level 2].
2) Set [F301: Auto-restart]. Depending on the characteristic of the application, [F302: Regenerative power ridethrough] = "1" is also effective.

Please reference latest AS3 Instruction Manual more details or latest information.