Pulse output width of input cumulative power

Function
Every time the integral input power reaches the cumulative power unit set by [F667: Pulse output step of input cumulative power], pulse signal can be output. You can display the power by pulse count without an external power meter.
Pulse output width is set by [F668: Pulse output width of input cumulative power].

Setting the parameters
This is a setting for pulse output from terminal [FP].
Set [F130: Terminal FP function 1] = "180: For input cumulative power"
Set the integral power unit with [F667: Pulse output step of input cumulative power], and set the pulse output width with [F668: Pulse output step of input cumulative power].