Browse the Frequently Asked Questions about the AS3 low voltage adjustable speed drive and if your answer is not included below, please take advantage of the Contact Us page so that a Toshiba representative may be of service.
Yes. The AS3 has a Heavy Duty (HD) rating and a Normal Duty (ND) rating. The ratings are designated on the nameplate of the drive.
230V: 2004-2037 Indonesia, others China
460V: 4004-4075 Indonesia, others India
600V: India
IP55: China
AS3P: Houston
Yes, the drive must be de-rated when operating on single-phase power. The rule-of-thumb is to use a drive that is double the HP size of the motor. Make note about removing RF/EMI filter.
230 V: Up to 75 HP HD and 100 HP ND
460 V: Up to 450 HP HD and 500 HP ND
Up to 600 ft without a long lead filter.
Reduction of Hazardous Substances Directive. RoHS restricts the use of hazardous materials in the manufacture of electrical equipment.
Yes, it is standard. Use it for Past trip monitoring or Calendar Functionality.
18 Pulse kits are available for Toshiba Approved panel shops.
Only available by using external third party front end products.
Yes. Flange-mount kits that allow the AS3 to be mounted in an enclosure with the heatsink out-the-back are available for all HP ratings.
Yes for 230V units up to 50HP HD/60HP ND and 460V units up to 100HP HD/125HP ND and the 250HP HD/350 ND model. All other units require a dynamic braking transistor option to be installed.
Yes, adjustment range includes: Frequency start, % current, time on and forward / reverse activation selection. [ F249 to F253 ]
230 V, HD: Nema1/ IP20 up to 50 HP and IP00 above 50 HP
230 V, ND: Nema1/ IP20 up to 60 HP and IP00 above 60 HP
460 V, HD: Nema1/ IP20 up to 100 HP and IP00 above 100 HP
460 V, ND: Nema1/ IP20 up to 125 HP and IP00 above 125 HP
Only for units that are frame size A6 and above.
100 kA with appropriate branch circuit protection. See Section 9.2 of the Instruction Manual.
Extended I/O terminal board(s), premium safety module, encoder feedback cards, 120V logic input card, dynamic braking transistor option.
It is not a separate item. The LCD keypad is detachable, and attached to the Door-Mount Kit purchased separately.
Yes. Nema 1, Nema 3R, Nema 4, Nema 4X, Nema 12, IP55. The AS3P is a Standardized Pre-Engineered N3R Package. Others available through Engineering.
Yes. All AS3 units have an internal DC link reactor (DCL.) For 460 V units 300 HP and above, the DCL ships loose to be installed in the field. Installation instructions are in the installation and operation manual.
STO is a standard which meets a SIL 3 category rating.
The mini-USB port is used for updating the keypad firmware by the factory.
Eight programmable Digital Inputs (F, R, RES, S1, S2, S3, S4, S5)
One programmable Form C Relay Output (FLA/FLB/FLC)
Two programmable Form A Relay Output (R1A/R1C, R2A/R2C)
One programmable Open Collector Digital Output (FP) Pulse-Train capable
Three Programmable Analog Inputs: (II) 4-20mA, (RR) 0-10 VDC, (RX) +-10 VDC
Two Programmable Analog Outputs: (FM, AM) Both 4-20mA or 0-10 VDC
Embedded STO Safety Terminal
One programmable Form C Relay Output (FLA/FLB/FLC)
Two programmable Form A Relay Output (R1A/R1C, R2A/R2C)
One programmable Open Collector Digital Output (FP) Pulse-Train capable
FLA: 250VAC (2A - PF=1, 1A when PF=.4), 30VDC (2A-Resistive Load)
Yes. ETB014Z adds (3) Relay Outputs.
Yes, this is called My Function on the AS3.
An RS485 cable or a generic ethernet cable will work.
Yes. Modbus RTU, Ethernet IP, and Modbus TCP are embedded. TWO Built-in Dual Port Ethernet IP are standard. This allows for "daisy-chain" ethernet installations, reducing the need for Ethernet Switches.
ProfiNet, Profibus DP, DeviceNet, EtherCAT, CAN Open (in addition to the embedded protocols)
Yes. The default setting is English and you can select among English, German, Italian, Spanish, Portuguese, and Chinese (simplified.), French, Russian, and Japanese.
No. Certain function have been replaced with My Function along with advanced PID features.
Heavy Duty (HD): 110% Continuous, 150% for 60 sec, 180% for 2 sec for frames A1 through A6, and 165% for frames A7 & A8 (250 to 450 Hp)
Normal Duty (ND): 105% Continuous, 120% for 60 sec, 150% for 2 sec
Ambient Temperature: 14° to 122°F (-10° to +50°C) or 140°F (+60°C) with Derate.
Current reduction necessary if above 1000 m for all frame sizes, reduced by 1% for each 100 m over 1000 m.
Range from 5% to 95% non-condensing.
Grounding setup cases. See manual for further detail.
Switching Switch 1 (SW1) to Sink (UP) or Source (down).
F295 - enables HOA switching during Auto Run (if required)
F701 - Current/Volts unit select, either % of full range, or V and A
F301 - Auto Restart - this is the "Catch a spinning motor" function
PrA displays when the STO terminal is OFF. To engage the STO terminal and clear the PrA code, move the SW1 switch to the Sink or Source position.
Dual PID is an improved method of PID control intended to minimize error and reach the desired set point quicker than traditional PID.
Yes, change parameter F248 (select the frequency to Coast) to upper limit frequency.
F1XX - Input / Output Parameters (Motor OL 2, 3 & 4)
F2XX - Frequency Parameters (Scaling, DC Injection, Jog, Motorized Pot, Jump Freq , Preset Speeds)
F3XX - Operation Parameters (auto restart, Retry, DBR, Carrier Freq, Brkae Function, PID, Tach, Sleep Functions)
F4XX - Motor Parameters (torque boost, tune, Load Sharing, Analog Input Bias & Gain)
F5XX- Acc / Dec Parameters - (Pattern Run, Shock Monitoring)
F6XX - Protection Parameters ( Stall, Emergency Stop, Phase Loss, Undercurrent, Under / Over Torque, Cooling Fan, Cummulative Run Time, Under/Over Voltage, Terminal AM/FM, Pulse Train)
F7XX - Panel Parameters (% or V/A, Mult factor, Monitor Modes, Panel Operations, Password, Trace, Easy Settings, Start Screen)
F8XX - RS485 Comm Parameters
F9XX - PM Parameters
A2XX - Pump Control
A3XX - Multi PID
A4XX - Positioning Control
A8XX - A9XX - My Function
Yes, on firmware V128 and higher.
Yes, on firmware V118 and higher.
Yes, use a 24V DC power supply on control terminals +SU and CC. This can allow you to program a drive before it is installed or retrieve parameters and past trip history during troubleshooting.
Yes, using our PCM002Z software and a USB-to-miniUSB cable. The configuration file can then be copied to the drive after power is applied.
Yes, you can apply a multiplier to the frequency to display motor RPM using parameter F702.
Yes, you can apply a multiplier to the frequency to display the output speed using parameter F702. This will be a linear display.
4 kHz for 230V units up to 40HP HD/50HP ND and 460V units up to 75HP HD/100HP ND. 2.5 kHz for all other units.
Yes. Input Terminals F, R, RES, and S1 support up to 3 functions each. Output Terminals R1A-R1C and FP support up to 2 functions each. For instruction, please see AS3 Application Guideline (TBD).
Yes, primary function (Function1) only.
You can generate a QR code on any Parameter, Fault, or Alarm by pressing the "Info" button. It's a lower-case i with a circle around it. QR codes are intended help users get general information about the AS3 drive and support when the AS3 is faulted. A QR code can be scanned by a smartphone and the user will be directed to the Toshiba website with information and troubleshooting techniques for the specific fault that occurred.
Yes, the standard keypad supports Copy/Paste functionality between multiple AS3's, or you can use Toshiba's free ASD Pro Software.
Up to 16 separate sets can be store.
Go to parameter F750 and set to a "2". Then press "Hand/Auto" button to select mode.
F711 through F718 are (8) User-Selectable Monitor settings. Example: Change F713 (Monitor Mode 3 display) from "4 - Output Voltage" to "1 - Frequency Command Value"